Search Results (415 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2025-9036 1 Rockwellautomation 1 Factorytalk Action Manager 2026-04-15 N/A
A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection.
CVE-2019-25276 1 Rockwellautomation 2 Factorytalk Activation, Studio 2026-04-15 7.8 High
Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions.
CVE-2024-6078 1 Rockwellautomation 1 Datamosaix 2026-04-15 N/A
CVE-2024-6078 IMPACT An improper authentication vulnerability exists in the affected product, which could allow a malicious user to generate cookies for any user ID without the use of a username or password. If exploited, a malicious user could take over the account of a legitimate user. The malicious user would be able to view and modify data stored in the cloud.
CVE-2025-9160 1 Rockwellautomation 2 Compactlogix, Compactlogix 5480 2026-04-15 N/A
A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution.
CVE-2025-7693 1 Rockwellautomation 1 Micro800 2026-04-15 N/A
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
CVE-2025-7353 1 Rockwellautomation 1 Controllogix 2026-04-15 N/A
A security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow.
CVE-2025-7971 1 Rockwellautomation 1 Studio 5000 Logix Designer 2026-04-15 N/A
A security issues exists within Studio 5000 Logix Designer due to unsafe handling of environment variables. If the specified path lacks a valid file, Logix Designer crashes; However, it may be possible to execute malicious code without triggering a crash.
CVE-2025-11862 1 Rockwellautomation 1 Verve Asset Manager 2026-04-15 N/A
A security issue was discovered within Verve Asset Manager allowing unauthorized read-only users to read, update, and delete users via the API.
CVE-2025-9437 1 Rockwellautomation 1 Armorstart Aop 2026-04-15 N/A
A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods.
CVE-2025-12807 1 Rockwellautomation 1 Factorytalk Datamosaix Private Cloud 2026-04-15 N/A
A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints.
CVE-2025-13824 1 Rockwellautomation 3 Micro820, Micro850, Micro870 2026-04-15 N/A
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
CVE-2025-7774 1 Rockwellautomation 1 Armorblock 5000 Io 2026-04-15 N/A
A security issue exists within the 5032 16pt Digital Configurable module’s web server. Intercepted session credentials can be used within a 3-minute timeout window, allowing unauthorized users to perform privileged actions.
CVE-2025-7973 1 Rockwellautomation 1 Factorytalk View 2026-04-15 N/A
A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation.
CVE-2025-9177 1 Rockwellautomation 1 1715-aentr Ethernet/ip Adapter 2026-04-15 N/A
A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage.
CVE-2024-10945 1 Rockwellautomation 1 Factorytalk Updater 2026-04-15 7.3 High
A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation.
CVE-2024-7567 1 Rockwellautomation 2 Micro850 Firmware, Micro870 Firmware 2026-04-15 N/A
A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration.
CVE-2025-11696 1 Rockwellautomation 1 Studio 5000 Simulation Interface 2026-04-15 N/A
A local server-side request forgery (SSRF) security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to trigger outbound SMB requests, enabling the capture of NTLM hashes.
CVE-2025-13823 1 Rockwellautomation 3 Micro820, Micro850, Micro870 2026-04-15 N/A
A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault.
CVE-2025-9042 1 Rockwellautomation 1 Flex 5000 Io 2026-04-15 N/A
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
CVE-2024-10943 1 Rockwellautomation 1 Factorytalk Updater 2026-04-15 9.1 Critical
An authentication bypass vulnerability exists in the affected product. The vulnerability exists due to shared secrets across accounts and could allow a threat actor to impersonate a user if the threat actor is able to enumerate additional information required during authentication.